Epoxy resin casting dry-type transformer series
Series SC10 35kV-class dry power transformer
    • Series SC10 35kV-class dry power transformer
Product Details

The parameters and specification of model SC10 35kV-class dry power transformer



Rated Capacity
     (kVA)

Voltage Combination

Tapping range
     %

Connection symbol

P0
     (W)

Pk
     (W)

Uk
     %

I0
     %

boundary dimension(mm)

LP
     (AN)
     dB

GT
     (kg)

High voltage(kV)

low voltage(kV)

long

wide

high

800

35

Or

38.5

3.15

6

6.3

10

10.5

11

 

 

 

±5
     ±2×2.5

 

 

 

 

 

 

Yyn0
       Dyn11

 

 

Yd11
YNd11

2220

9350


0.6

1980

1020

2050

52

3500

1000

2640

10860

0.6

2050

1020

2150

52

4000

1250

3100

12850

0.6

2150

1020

2250

53

4700

1600

3650

15400

0.5

2300

1370

2380

53

5700

2000

4180

18140

0.5

2300

1370

2450

54

6400

2500

4800

21720

0.5

2660

1370

2460

55

7000

3150

5960

24370

0.4

2600

1370

2505

56

9520

4000

6940

29280

0.4

2990

1370

2550

57

10500

5000

8270

34760

0.4

2990

1370

2660

58

12800

6300

9780

40610

0.3

3270

1800

2775

59

16900

8000

        ±3×2.5

11200

45810

0.3

3800

1800

2820

60

18760

10000

12800

55250

0.3

3800

1800

2830

60

26210

12500

6  6.3

10  10.5

11

15560

64230

0.2

4210

1800

3300

62

30000

16000

19110

75560

0.2

4210

1800

3370

62

38500

20000

22670

85000

0.2

4400

2000

3450

62

43500

Inquiry Now
Message *
Name *
Phone
Email*
    
    
>>Drag the slider to verify<<
Other Products

Map

Add:No.11 YulanRoad Zhonglou Economical develop Zone of Changzhou

Contact Us

  • Head-Office: 0086-519-83273841Sales Departtment Tel: 0086-519-8328176083972779
  • E-mail: qinzhixin@czhua-di.com
  • Zip: 213016
  • Fax: 0086-519-83973779
  • Cable: 6239
ewmMobile
Share: